Cooling
Cooling Tower capacity of 0.5 MW
A water flow at pressure differential 60 PSI at inlet temperature 45ºC permits operation at full power (378 kW)
Flow rate of 11 liters/min and temp. rise of 14ºC per pancake
- Total water flow through magnet: 352 liters/min
12.5 kW are dissipated in cooled buss
Monitoring:
- Temp. rise: Auto-reset Klixons set at 70ºC
- Water flow: Paddle Flow meters